CASTLE EURO Spécifications Page 187

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 198
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 186
Castle Care-Tech Ltd Engineering
Page 25-2 Chapter 25
Programming the
Outputs:
Select Output type 035 as
described on page 13-2
Output xx [035]
Follow Zone
Press YES
Follow Type
Follow [0]
Use
D
or number keys to
select type required:
0 = Follow
1 = Timed
2 = Latched
Press YES
IF
TIMED
selected:
Output On For
[000]
Select time (in seconds)
output required to be live
for.
Press YES
For ALL selections:
Follow What?
Zone [0]
Use
D
or number keys to
select type required:
0 = Zone
1 = Shunt List
2 = Ward
3 = Area
Press YES
Follow When?
When Set [0]
Use
D
or number keys to
select type required:
0 = When Set
1 = When Unset
2 = Always
Press YES
Zone to Follow
[001]
OR
Area to Follow
etc
dependant upon selection
made).
Use
D
or number keys to
select zone (etc.) number
required to follow
Press YES.
IF
LATCHED
OPTION
SELECTED ONLY
Reset by Zone
[001]
Insert number of zone to be
used for performing the
reset.
This may be a suitably
located switch, etc. wired as
a zone, or any other zone
on the system.
IN ALL CASES:
Option to programme next
output.