CASTLE EURO Spécifications Page 147

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 198
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 146
Castle Care-Tech Ltd. Engineering
Page 17 - 2 Chapter 17
TERMINAL CONNECTIONS
If the Output Module is plugged onto an
Intelligent Power Supply, all connections
are automatically made to draw current
from the power supply, and to use the
system diagnostic capabilities to control
the power supply.
A set of pins is provided that will accept a
plug-on relay interface to provide higher
current drive outputs.
These pins are also compatible with
industry-standard STUs, etc. However, the
INPUTS from the device are NOT currently
monitored.
An alternative module will be available
with ONLY the STU pin outputs.
Terminal Allocations
D RS.485
1 0v
2 +12v
3
A
4
B
Q Outputs
1 Output 1
-
3 Output 2
-
5 Output 3
-
7 Output 4
-
9 Output 5
-
11 Output 6
-
13 Output 7
-
15 Output 8
-
17 Output 9
-
19 Output 10
-
21 Output 11
-
23 Output 12
-
25 Output 13
-
27 Output 14
-
29 Output 15
-
31 Output 16
-
All even numbered
terminals are+12v
G
(ON PSU PCB)
AC Input
1 Mains Earth
2 AC in
3 AC in