Manual Euro-MERiDIAN
Chapter 1 Page 1 - 3
"Sequentially Confirmed" alarm systems:
Please note the following sequence of events for 'unconfirmed'
alarm activations, where "unset with portable ACE" is used, and
ensure that all potential users are made aware of these system
responses:
Local response Signalled response to ARC
System Set Exit time ends 'Set' signal
Alarm
generated
Alarm sounds 'Intruder' signal (Code 3)
'Siren time'
ends
Alarm silences -
BEFORE END OF 'CONFIRMATION TIME:
Key-holder
opens FX
zone
"Entry Time" starts,
Alarm sounds
-
Key-holder
unsets system
Sounders silenced 'Unset' signal,
'Intruder' signal restores
Note that what appears to be an alarm condition is generated.
However, this is NOT signalled, and has NO effect on the system
response for "confirmation" purposes, but provides the maximum
possible deterrent to a potential intruder returning to the site after
the 'unconfirmed' alarm has silenced.
In the event of the system NOT being unset before the end of the entry
time, confirmed response will follow after the triggering of the NEXT zone
OFF the entry route, provided that 'Confirm Timer' has not expired.
If the "confirm timer" expires, the system will perform a complete
"reinstatement" as prescribed by DD243:2002, with 'zone omit at rearm'
signal if appropriate. A keyholder entering after that time will receive
normal system response (ie entry time).